Respuesta :
Answer:
hello your question has a missing information
The other is Δ-connected with an impedance of (60 - j45) ohm per phase.
answer : A) 5A ∠0° ,
p( real power ) = 1800 and Q ( reactive power ) = 0 VAR
B) 193.64 v
C) current at load 1 = 2.236 A , current at load 2 = 4.472 A
D) Load 1 : 450 watts(real power ) , 600 VAR ( reactive power )
Load 2 : 1200 watts ( real power ), -900 VAR ( reactive power )
Explanation:
First convert the Δ-connection to Y- connection attached below is the conversion and pre-solution
A) determine the current, real power and reactive power delivered by the sending-end source
current power delivered (Is) = 5A ∠0°
complex power delivered ( s ) = 3vs Is
= 3 * 120∠0° * 5∠0° = 1800 + j0 ---- ( 1 )
also s = p + jQ ------ ( 2 )
comparing equation 1 and 2
p( real power ) = 1800 and Q ( reactive power ) = 0 VAR
B) determine Line-to-line voltage at the load
Vload = √3 * 111.8
= 193.64 v
c) Determine current per phase in each load
[tex]I_{l1} = Vl1 / Zl1[/tex]
= [tex]\frac{111.8<-10.3}{50<53.13}[/tex] = 2.236∠ 63.43° A hence current at load 1 = 2.236 A
[tex]I_{l2} = V_{l2}/Z_{l2}[/tex]
= [tex]\frac{111.8<-10.3}{25<-36.87}[/tex] = 4.472 ∠ 26.57° A hence current at load 2 = 4.472 A
D) Determine the Total three-phase real and reactive powers absorbed by each load
For load 1
3-phase real power = [tex]3I_{l1} ^{2} R_{l1}[/tex] = 3 * 2.236^2 * 30 = 450 watts
3-phase reactive power = [tex]3I_{l1} ^{2} X_{l1}[/tex] = 3 * 2.236^2 * 40 = 600 VAR
for load 2
3-phase real power = [tex]3I_{l1} ^{2} R_{l2}[/tex] = 1200 watts
3-phase reactive power = [tex]3I_{l1} ^{2} X_{l2}[/tex] = -900 VAR
The sum of load powers and line losses, 1800 W+ j0 VAR and The line voltage magnitude at the load terminal is 193.64 V.
(a) The impedance per phase of the equivalent Y,
[tex]\bar{Z}_{2}=\frac{60-j 45}{3}=(20-j 15) \Omega[/tex]
The phase voltage,
[tex]\bold { V_{1}=\frac{120 \sqrt{3}}{\sqrt{3}}=120 VV }[/tex]
Total impedance from the input terminals,
[tex]\bold {\begin{aligned}&\bar{Z}=2+j 4+\frac{(30+j 40)(20-j 15)}{(30+j 40)+(20-j 15)}=2+j 4+22-j 4=24 \Omega \\&\bar{I}=\frac{\bar{V}_{1}}{\bar{Z}}=\frac{120 \angle 0^{\circ}}{24}=5 \angle 0^{\circ} A\end{aligned} }[/tex]
The three-phase complex power supplied [tex]\bold {=\bar{S}=3 \bar{V}_{1} \bar{I}^{*}=1800 W}[/tex]
P =1800 W and Q = 0 VAR delivered by the sending-end source.
(b) Phase voltage at load terminals will be,
[tex]\bold {\begin{aligned}\bar{V}_{2} &=120 \angle 0^{\circ}-(2+j 4)\left(5 \angle 0^{\circ}\right) \\&=110-j 20=111.8 \angle-10.3^{\circ} V\end{aligned} }[/tex]
The line voltage magnitude at the load terminal,
[tex]\bold{\left(V_{ LOAD }\right)_{L-L}=\sqrt{3} 111.8=193.64 V(V }[/tex]
(c) The current per phase in the Y-connected load,
[tex]\bold {\begin{aligned}&\bar{I}_{1}=\frac{\bar{V}_{2}}{\bar{Z}_{1}}=1-j 2=2.236 \angle-63.4^{\circ} A \\&\bar{I}_{2}=\frac{\bar{V}_{2}}{\bar{Z}_{2}}=4+j 2=4.472 \angle 26.56^{\circ} A\end{aligned} }[/tex]
The phase current magnitude,
[tex]\bold {\left(I_{p h}\right)_{\Delta}=\frac{I_{2}}{\sqrt{3}}=\frac{4.472}{\sqrt{3}}=2.582 }[/tex]
(d) The three-phase complex power absorbed by each load,
[tex]\bold {\begin{aligned}&\bar{S}_{1}=3 \bar{V}_{2} \bar{I}_{1}^{*}=430 W +j 600 VAR \\&\bar{S}_{2}=3 \bar{V}_{2} \bar{I}_{2}^{*}=1200 W -j 900 VAR\end{aligned}}[/tex]
The three-phase complex power absorbed by the line is
[tex]\bold{\bar{S}_{L}=3\left(R_{L}+j X_{L}\right) I^{2}=3(2+j 4)(5)^{2}=150 W +j 300 VAR }[/tex]
Since, the sum of load powers and line losses,
[tex]\bold {\begin{aligned}\bar{S}_{1}+\bar{S}_{2}+\bar{S}_{L} &=(450+j 600)+(1200-j 900)+(150+j 300) \\&=1800 W +j 0 VAR\end{aligned} }[/tex]
To know more about voltage,
https://brainly.com/question/2364325